Bird - The RF Experts
6150-ALM-01

NFPA Compliant Alarm Panel


Mission Critical Reliability


The Bird NFPA alarm panel meets all NFPA code requirements for a dedicated alarm panel within the fire command center. To report the status of all RF emitting devices and system component locations, the annunciations are 5 Bicolor LEDS (Green=No Alarm, Red=Alarm), dedicated to the 5 failure modes to annunciate. The monitoring panel provides a clear visual display and labeled indications of the required alarms for a single booster. Alarm triggers are through Form C Contacts on the Booster.

For increased flexibility, the Bird NFPA Alarm Panel can be powered with the Battery Backup Unit or any other DC power source from 12 to 24 VDC.

Downloads:
product specifications:
Item No
6150-ALM-01
Item Name
NFPA Alarm Panel
Alarm
Input: Form C Dry contacts
(Normally Closed = Green)
Display: LED

Alarms Displayed:
AC Power Failure
Battery Charger Failure
Battery <30% remaining
Donor Antenna Failure
Booster Failure
Power Input
External DC supply, 12~24 V, 100 mA
Connectors
Direct Connection
Operating Temperature
Operating: 32 to 122 °F (0 to 50 °C)
Enclosure
NEMA 4 (Red)
Size
8.28" x 6.28" x 3.7" (210 x 160 x 94 mm)
Weight
2 lb (0.91 kg)